Product Specs
Generator Set Specifications
- Standby Rating
- 2250 kVA
- Prime Power Rating
- 2000 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
- Voltage
- 380 to 11000 Volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Mission Critical, Prime, Continuous
- Maximum Rating
- 2250 kVA
- Minimum Rating
- 1750 kVA
Engine Specifications
- Engine Model
- 3516B TA, V-16, 4-Stroke Water-Cooled Diesel
- Bore
- 6.69 in
- Stroke
- 7.48 in
- Displacement
- 69 in
- Compression Ratio
- 14.0:1
- Aspiration
- TA
- Fuel System
- Electronic unit injection
- Governor Type
- Adem™3
Generator Set Dimensions
- Length - Minimum
- 233.4 in
- Length - Maximum
- 6377 in
- Width - Maximum
- 90 in
- Height - Maximum
- 93.2 in
- Dry Weight - Genset (minimum)
- 31900 lb
- Dry Weight - Genset (maximum)
- 40320 lb
Standard Equipment
-
- Air Inlet System
-
- Air cleaner; single element canister type
-
- Cooling
-
- Package mounted radiator
-
- Exhaust
-
- Exhaust flange outlet
-
- Fuel
-
- Primary fuel filter with integral water separator
- Secondary fuel filters
-
- Generator
-
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
-
- Power Termination
-
- Busbar
-
- Control Panels
-
- Engine cool-down timer
- Frequency (Hz)
- DC volts
- Volts (L-L & L-N)
- Customizable screens
- Limiter and exciter diode monitor
- Power factor (per phase & average)
- 1 Programmable relay outputs (Form C
- Text alarm/event descriptions
- Speed adjust
- 1 Programmable digital outputs
- Overspeed - Emergency stop
- 4 Programmable relay outputs (Form A)
- Emergency stop - Failure to start (overcrank)
- Reverse reactive power (kVAr) (32RV)
- 6 Customer programmable digital inputs
- Customer data link (Modbus RTU)
- Emergency stop pushbutton
- Environmental sealed front face
- kW-hr (total) - kVAr-hr (total)
- Cat connect
- Load histogram feature
- RPM - DC volts
- Failure to start (overcrank)
- Serial annunciator module data link
- Coolant temperature
- Operating hours
- kW (per phase, average & percent)
- IVR includes:
- Low coolant temperature
- Reactive droop capability
- Generator set packages include Caterpillar's voltage regulator
- Digital indication for:
- KVAR/PF modes
- Lamp test
- Controls:
- PLC functionality
- 0 True RMS AC metering, 3-phase, +/-2% accuracy
- Oil pressure (psi, kPa or bar)
- Generator mounted - rear facing
- Amps (per phase & average)
- Low coolant level
- 3 Analog inputs
- Reverse power (kW) (32)
- 24 Volt DC operation
- Over/under voltage (2 7/ 59)
- Over/under frequency (81 o/u)
- RFI suppression
- 3 Phase voltage sensing
- Cat ECS 100
- Alarm acknowledge
- Auto/start/stop control
- kVA (per phase, average & percent)
- Min / max exciter
- Engine cycle crank
- Low oil pressure
- Accessory module data link
- High coolant temperature
- Warning/shutdown with common LED indication of shutdowns for:
- Communications:
- Overcurrent (50 / 51)
- Number of I/O varies on options selected
- Programmable protective relaying functions:
-
- Control Panel
-
- Cat ECS Genset controller
-
- Cooling System
-
- Certified standard PGS provided
-
- Exhaust System
-
- Dry exhaust manifold
- Flanged faced outlet(s)
-
- Fuel System
-
- Secondary fuel filters
- Flexible fuel lines - shipped loose
- Fuel cooler; not included with packages without radiator
- Fuel priming pump
-
- General
-
- Paint - Caterpillar yellow except rails and radiators gloss black
- Right hand servicing
- Flywheel and flywheel housing - SAE No. 00
- SAE standard rotation
- Caterpillar yellow with high gloss black rails and radiator
-
- Generator And Attachments
-
- Busbar connections, right side extension box, bottom cable entry
- 3 Phase brushless, Salient pole
- Form wound - Permanent magnet excitation (PMG)
- Anti-condensation space heater
- Busbar connections, top center mounted, top cable entry
- 6 Leads
- Winding temperature detectors
- Class H temperature rise at 40C ambient (125C prime / 150C standby)
- Form wound
- Internal excitation (IE)
- NEMA Class H insulation
- Low voltage:
- Random wound
- High voltage:
- Medium voltage:
- Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby
- Permanent magnet excitation (PMG)
- NEMA standard hole pattern
-
- Governing System
-
- ADEM A3
-
- Literature
-
- Parts book
-
- Lubrication System
-
- Fumes disposal
- Oil drain lines and valve
- Lubricating oil
- Integral lube oil cool
- Oil filter, filler and dipstick
- Gear type lube oil pump
-
- Mounting System
-
- Rails - Engine/generator/radiator mounting
- Anti-vibration mounts (shipped loose)
- Rubber anti-vibration mounts - shipped loose
-
- Starting System
-
- Battery and battery rack w/cables
- 24 Volt electric starting motor
- Battery disconnect switch
- 45 Amp Charging alternator
Attachments
-
- Control System
-
- EMCP 4.4
-
- Exhaust
-
- Exhaust mufflers
-
- Air Inlet System
-
- Single element filter
- Dual element air cleaner
-
- Generator
-
- Oversize and premium generators
- Permanent magnet excitation (PMG)
- Anti-condensation heater
- Internal excitation (IE)
-
- Cooling System
-
- Standard ambient radiators
- Coolant
- Optional installed radiators
- Optional installed ATAAC radiators
- Standard ambient ATAAC radiators
- Water level switch gauges
-
- Power Termination
-
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
-
- Crankcase System
-
- Ventilation system
- Explosion relief valves
- No explosion relief valves
-
- Control Panels
-
- Remote monitoring software
- Load share module
- Digital I/O module
- Generator temperature monitoring & protection
-
- Exhaust System
-
- Y Adapters
- Elbows
- Mufflers
- Flange and exhaust expanders
- Clean emission parts
- Tier 4 dosing cabinet
- Exhaust offset
- Flexible fittings
- Tier 4 clean emission MOD Kits
- Flanges
- Tier 4 clean emissions module
-
- Fuel System
-
- Primary fuel filter
- Fuel priming pumps (Tier 4) - Manual or electric
-
- Starting/charging
-
- Air starting motor with control and silencer
- Charging alternator
- Oversize batteries
- Heavy duty starting system
-
- Generators And Attachments
-
- Differential current transformers (DCT)
- Thermostat for space heater
- Differential current transformers (DCT) 8.7 kV and 15 kV classes
- Alternator air cleaner
- Generator conversion
- Space heater
- Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
- Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
-
- Instrumentation
-
- Pyrometer and thermocouples
-
- General
-
- Special paint (Colors other than Caterpillar yellow or high performance paints)
- US aid emblem
- EEC Declaration of Conformity
- Automatic transfer switches (ATS)
- CSA Certification
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- Enclosures: Sound attenuated, weather protective
- The following options are based on regional and product configuration:
- Integral & sub-base fuel tanks
- EU Certificate of Conformance (CE)
- Integral & sub-base UL listed dual wall fuel tanks
- UL 2200 package
-
- Lubrication System
-
- Lube oil in standard sump
- Oil level regulator
- Prelube pumps
-
- Mounting System
-
- IBC vibration isolators
- Spring type vibration isolators
- Puck style low efficiency isolators
-
- Mounting
-
- IBC isolators
-
- Power Connections
-
- Neutral ground connections
- Center post busbars
- Low voltage Circuit breakers
- 2700 Frame, four lead, four terminal
- Right side power connections
- Ground cables between generator and terminal box
- Rear power connections
- Left side power connections
-
- Special Tests / Reports
-
- Standard engine test charge
- Torsional vibration analysis reports
- PGS Test report @ 1.0 power factor
- Fuel consumption test
- IBC Certification
- Canadian Standards Association certification
- PGS Test report @ 0.8 power factor
- Generator test report
- Generator set fuel consumption test
- OSHPD Certification
-
- Starting And Charging
-
- Air starting motors
- Jacket water heaters
- Starter cover
- 10, 20, 35 and 50 Amp Battery chargers
- Air pressure regulator
- Electric starting motors
- Engine barring device
- 24 Volt battery set - Dry
-
- Extended Service Coverage
-
- Platinum, Gold and Silver coverage