Product Specs
Generator Set Specifications
- Maximum Rating
- 8.8 ekW
- Minimum Rating
- 8.0 ekW
- Emissions/Fuel Strategy
- R96/EUIIIa Equivalent
- Voltage
- 110 to 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Prime
Engine Specifications
- Engine Model
- C1.1, In-line 4, 4-cycle diesel
- Bore
- 3 in
- Stroke
- 3.2 in
- Displacement
- 69 in³
- Compression Ratio
- 23.0:1
- Aspiration
- Naturally Aspirated
- Fuel System
- Indirect Injection
- Governor Type
- Mechanical
Generator Set Dimensions
- Length - Maximum
- 55.1 in
- Width - Maximum
- 24.4 in
- Height - Maximum
- 39.2 in
Standard Equipment
-
- Air Inlet System
-
- Air cleaner; light duty with disposable element
-
- Control Panel
-
- GCCP 1.3
-
- Cooling System
-
- Coolant drain line with valve
- Caterpillar extended life coolant
- Radiator and cooling fan with guards
- Fan drive, battery charging alternator drive
-
- Exhaust System
-
- Stub pipe, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
-
- Fuel System
-
- Base, formed steel with single wall integral 8-hour fuel tank
- Standard open set fuel tank/base supplied
-
- Generators And Generator Attachments
-
- 12 Leads
- IP23 Protection
- Segregated low voltage (AC/DC) wiring panel
- Circuit breaker, IEC, 3 pole, mounted in tower panel
- Voltage regulator (single phase sensing)
- Tower panel, IP22, bottom cable entry
-
- Governing System
-
- Mechanical governing system
-
- Lube System
-
- Lubricating oil
- Oil drain line with valve
-
- Mounting System
-
- Includes lifting provisions and termination points for coolant
- Captive linear vibration isolators between base and engine-generator
-
- Starting / Charging System
-
- 12 Volt battery with rack and cables
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
Attachments
-
- Alternator Options
-
- Coastal insulation protection
-
- Certificates
-
- European upgrade to STD set for CE certificate
- Global certification for CIS
-
- Circuit Breakers
-
- Padlockable breaker device
- 4 Pole Circuit breaker
-
- Control Panel
-
- Battery charger
- Volt free contacts for common alarm
- Volt free contacts for genset running
- Emergency stop with key
- GCCP 1.3
-
- Cooling System
-
- Coolant heater
-
- Enclosures
-
- Single point lift for enclosure
- Sound attenuated enclosure (GALV)
-
- Fuel System
-
- Fuel transfer control
- Base feet
- 1000 hr extended service interval
- Skidbase for enclosures
- Skidbase for open sets
- DEFRA bunded fuel tank
- Low fuel level alarm
-
- Mounting Options
-
- Industrial silencer removal
- Battery removal
- Silencer installation kit
-
- Special Test And Inspection
-
- PGS Test report @ 1.0 power factor
-
- General
-
- Radiator stone guard
- Packing case - canopied set
- Packing case - compact set